| UMPX-12 Portable Step Up Voltage and Frequency Converter Specification |
| Models |
UMPX-12 |
| Output |
| Capacity |
2700W/3000VA |
| Output Voltage |
200V/220V/230V/240V (Selectable) |
| Maximum Output Current |
9.0 Amp (120V Input) / 12.5 Amp (200V+ Input) |
| Output Peak Current (<250mS) |
40 Amp |
| Maximum Continuous Load |
2700W |
| Maximum Peak Load |
3500W (Tested Under 240Vac Input) |
| Voltage Regulation |
±2% of selected output voltage |
| Output Frequency |
50Hz or 60Hz (selectable) |
| Output Frequency Synchronization |
60±0.01Hz or 50±0.01Hz (independent of input frequency) |
| Crest Factor |
3:1 |
| Voltage Waveform |
Sine Wave |
| Total Harmonic Distortion (Resistive Load) |
<2% |
| Total Harmonic Distortion (Reactive Load) |
<3% |
| Standby Power |
27W |
| Output EMI Filter |
150Khz - 30Mhz |
| Output RFI Filter |
30Mhz - 1000Mhz |
| Clamp Level |
400V Peak |
| Efficiency (Input to Output) |
>87% |
| Output Connection From Mains |
| Ground |
Input and Output Ground are Connected |
| Neutral |
Input and Output Neutral Connected (after EMC inductor )\nIsolation Transformer is not required |
| Input |
| Nominal Voltage |
120V/240V |
| Input Voltage Range |
90Vac ~ 285Vac |
| Input Current |
20 Amp |
| Input Frequency Range |
45Hz - 70Hz |
| Input Neutral Auto Detect and Correct |
No |
| Wall-Outlet Type Required |
Includes 8 Input Plug Types |
| Phase |
Single |
| Noise Filtering |
Full-Time EMI/RFI Filtering |
| Input EMI Filter |
150Khz -30Mhz (class A) |
| Input RFI Filter |
30Mhz - 1000Mhz (class A) |
| Overcurrent Protection (Input) |
By Re-Settable; Overcurrent Protector |
| Power Factor |
≧ 0.98 |
| Switch-On Surge (In-Rush Current) |
<100A, 3mS |
| Voltage Interruption Ride Through |
10mS |
| Protection |
| Overcurrent Protection (Output) |
Overload Alarm Level: 100% ~ 129% (alarm after 1 minute delay, shutdown after 1 minute alarm);\nOverload Shutdown Level: 130% (shutdown after 2 second delay) |
| Short-Circuit Protection |
Pulsating Type, 37A Peak; Auto-Restart time: 30 seconds |
| Over-Temperature Protection |
When the temperature inside is over 76℃, the LCD will show the Over-Temperature Symbol.\nIf the temperature continues rising to 85℃, the buzzer alert for high temperature is activated and the CPU will shut down the output voltage. The CPU will resume output voltage automatically once the temperature drops to 75℃ or lower.\n |
| Indicators and Alarms |
| LCD Display |
Displays Input Voltage, Output Voltage, Output Frequency, Temperature, Load Level. Selectable Output Voltage and Output Frequency |
| Indicator - Load Level |
LCD Displays Current Usage Level of Total Available Capacity |
| Indicator - Overload |
LCD Shows Overload Symbol |
| Indicator - Over-Temperature |
LCD Shows Over-Temperature Symbol |
| Audible Alarms |
Overload Alarm, Short-Circuit Alarm, Over-Temperature Alarm |
| Audible Alarm - Overload |
Continuous Alarm |
| Audible Alarm - Short-Circuit |
Every other 2 seconds, 32 beeps in 2 seconds |
| Audible Alarm - Over-Temperature |
Every other 2 seconds, 32 beeps in 2 seconds |
| Environmental and Safety |
| Sealed Solid-State Electronics |
No |
| Operating Temperature |
Up to 1500 meters: 0℃ to 40℃ (32℉ to 104℉) |
| Transit/Storage Temp |
-15℃ to 55℃ (5℉ to 131℉) |
| Relative Humidity |
5 – 95% Non-Condensing |
| Operating Altitude |
0 ~ 3000 Meters |
| Moisture Sensitivity |
Internal Fan |
| Audible Noise |
≦45 dBA (at 1 meter from surface of unit) |
| Safety Markings |
CE & BSMI |
| Cooling |
| Cooling Method |
Forced Air Cooling by Internal Fan |
| Natural Ventilation Cooling |
No |
| Internal Fans |
Internal fan will run at low speed continuously when the temperature inside is low. Fan speed increases as temperature rises. When internal temperature is over 60° C, the internal fan runs at full speed |
| External Emergency Cooling Fan |
Yes |
| Physical |
| Product Dimensions (L) in |
17 |
| Product Dimensions (W) in |
10 |
| Product Dimensions (H) in |
4 |
| Product Dimensions (L) cm |
43 |
| Product Dimensions (W) cm |
25 |
| Product Dimensions (H) cm |
10 |
| Product Weight (lbs) |
15 |
| Product Weight (kgs) |
6.8 |
| Carton Dimensions (L) in |
25 |
| Carton Dimensions (W) in |
14 |
| Carton Dimensions (H) in |
20 |
| Carton Dimensions (L) cm |
63 |
| Carton Dimensions (W) cm |
36 |
| Carton Dimensions (H) cm |
51 |
| Shipping Weight (lbs) |
45 |
| Shipping Weight (kgs) |
20.4 |
| Warranty, Quality Control, and International Approvals |
| Warranty |
2 Years, Full Replacement |
| Quality Control Standard |
ISO9001 |
| UL-Ulus |
Not Applicable |
| UL 1012 |
Not Applicable |
| UL-cUL |
Not Applicable |
| DEMKO-CB |
Not Applicable |
| TUV/SUD-CB |
Not Applicable |
| FCC Part 15 |
Not Applicable |
| EMC |
Not Applicable |
| Other |
|
| Standard Accessories |
8 Input Power Cord Types: A, B, 8303, NEMA 5-20P, NEMA 6-20P, C/F/E, G, N\nC-19 Connecting Cord\nHard Travel Case |
| Wall Mountable |
No |
| Appliance Mountable |
No |
| Compatibility |
| Output Compatibility with UPS |
Yes |
| AC Input Generator Compatible |
Yes |